Danfoss Hansen eXtra-dense pluggable optics Blind Mate liquid Connector (XBMC)
One partner, every solution

Fact sheet > Danfoss Hansen eXtra-dense pluggable optics Blind Mate liquid

 

Danfoss Hansen XBMC (eXtra-Dense Pluggable Optics Blind-Mate Connector) is a purpose-built liquid cooling connector designed to meet XPO technical specifications version 0.99 for next-generation pluggable optics applications.

Engineered for ultra-high-density deployments, XBMC is the smallest quick-disconnect coupling available for data centre liquid cooling, enabling reliable blind-mate connectivity, maximising rack density, and simplifying installation and serviceability in space-constrained environment.

Danfoss Hansen eXtra-dense pluggable optics Blind Mate liquid Connector (XBMC)
Fact sheet > Danfoss Hansen eXtra-dense pluggable optics Blind Mate liquid


 

Product Features*

- Designed per XPO specifications (V 0.99) to support XPO infrastructure
- Push-to-connect design
- Smallest blind mate QD developed with optimized flow and limited pressure drop for optimized cooling system efficiency
- Flat-face dry break design to avoid spillage during connection & disconnection
- ”Blind-connection” with self-alignment feature of +/-0.5 mm radial offset
- Standard material: Stainless steel (304) & EPDM-P (Peroxide-cured) provide broad fluid compatibility
and highest corrosion resistance
- QR Code identification to help track parts
- Operating temperature: +17° to +65°C (62.6°F to 149°F)
- Spillage: <0.02 cc max
- Compliant to RoHS REACH, IEC 62368 G15 requirements

These will be refined based on the results of our internal testing and validation process.

 

Solutions to your liquid cooling challenges

Switch tray solutions

Danfoss’ direct-to-chip cooling solutions extend into the racks through efficient routing of flexible, kink-free hoses, and leak free, helium-tested couplings. Danfoss has a comprehensive portfolio of premium fluid conveyance products to meet your thermal management system needs.

 

Applications & Markets

- Liquid-cooled XPO optical switches and pluggable optics used in next-generation AI and hyperscale data centres

Part/Order number

11432427 Plug Customized sealing M4X0.7
11432428 Socket Customized sealing M5X0.8

 

 

 

Beijing Hansen Fluid Technology Co., Ltd.
Danfoss Data center liquid cooling authorized distributor
One partner, complete solution ~ liquid cooling Products Solutions

Add:Rm2115, Tower C, Wangjing SOHO, Chaoyang district Beijing , China
Tel:010-8428 2935 , 8428 3983
Mobile: 13910962635 WeChat
Fax:010-8428 8762

Http://www.hansenfluid.com
E-mail:max_yang@hansenfluid.com

京ICP备2023024665号
京公网安备 11010502019740

Since 2007 Strong Distribution & Powerful Partnerships